CONTACT US
Product Overview:
The High-Pressure CO₂ Automatic Fire Extinguishing System is a modern fire protection technology that utilizes carbon dioxide gas as the extinguishing agent. This system benefits from a wide availability and low cost of CO₂, offering low toxicity and excellent electrical insulation properties. It can be stored long-term without corrosion or damage to protected materials after discharge. With increasing emphasis on protecting the atmospheric ozone layer, CO₂ has become one of the primary agents for gas-based fire suppression.
Key Features:
- Eco-Friendly Extinguishing Agent: CO₂ is a green fire extinguishing agent with a short atmospheric residence time, minimizing its environmental impact.
- Wide Application: Suitable for locations with regular human occupancy, ensuring personnel safety while effectively controlling fire risks.
- Automated Functionality: The system can connect to automatic alarm control systems to enable automatic fire extinguishing, enhancing response speed.
- Multiple Activation Methods: In emergencies, users can choose between electrical manual activation or mechanical emergency manual activation, increasing flexibility and reliability.
- Non-Damaging Extinguishing: The discharged CO₂ does not corrode or damage protected items, making it ideal for safeguarding critical equipment and facilities.
Applications:
- Industrial Locations: Widely used in chemical plants, electronics factories, and mechanical manufacturing environments where fire hazards exist.
- Commercial Buildings: Suitable for large shopping malls, offices, hotels, and other public places, ensuring personnel safety and property protection.
- Data Centers: Applied in data centers and server rooms to protect sensitive equipment from fire threats.
- Petrochemical Industry: Particularly effective in flammable and explosive environments within the petrochemical sector, significantly reducing fire risks.
- Marine and Aviation: Used in ships and aircraft to ensure the safety of passengers and equipment.
Parameter | Value |
Extinguishment types | Total flooding type |
Starting bottle group volume | 4L |
Volume of storage cylinder | 70L |
Starting mode | Auto start, manual start, mechanical emergency start |
Storage pressure | (20℃) 5.7MPa |
Starting gas supply | Nitrogen (6.6MPa) |
Max. working pressure | (50℃) 12.4MPa |
Starting electromagnetic starter current/voltage | 1.6A DC 24V |
Fire extinguishing agent filling density | 600 kg/m³ |
Using environmental temperature | 0℃-50℃ |
Fire extinguishing agent blowdown time | <60s |
Select valve installation height | ≤1700mm |